Self-Tuning - gefran 650 Installation And Instruction Manual

Pid temperature controllers
Hide thumbs Also See for 650:
Table of Contents

Advertisement

Process variable
Variabile di
processo
Peak
Picco
4.
Calculate the PID parameters:
• Proportional Band P.B. value
Peak
P.B. =
V
- V
max
min
where V
- V
is the scale interval.
max
min
• Integral Time value It = 1.5 x T
• Derivative Time value dt = It / 4
5.
Switch the controller to manual.
6.
Set the calculated parameters (re-enable PID control by
setting a cycle time for relay output if necessary).
7.
Switch to automatic.
8.
To check optimization of the parameters, change the
setpoint value if possible and check transitory behavior:
if oscillation persists, increase the Proportional Band
value; on the other hand, if the response is too slow,
decrease the value.

5.10.3. Self-Tuning

Self-Tuning is a simplified and automatic tuning mode based
on the process state.
The purpose of Self-Tuning is to calculate optimum control
parameters at the start of the process.
The variable (for example, temperature) must be the one me-
asurable at zero power (room temperature).
You can automatically start tuning at every power-on or start
it by means of the appropriately configured ( ) key.
The procedure runs automatically by optimizing the approa-
ch in relation to the real temperature value, in case of (relay,
solid-state, Triac) control output, with automatic calculation
of optimal cycle time CY.TIM.
At the end of the procedure, the following new PID parame-
ters are saved:
proportional band,
integral and derivative times, calculated for the cur-
rent action (heat or cool).
In case of dual action (heat + cool) the parameters are
calculated automatically separately for the two actions.
Active tuning condition is signaled on the display by an LED
80208G_MHW_650-1250-1350_01-2017_ENG
T
Time
Tempo
x 100
5. Examples and applicative notes
Attention! Self-Tuning is not applicable with an
ON/OFF control.
Notes
For the programmer model, if Self-Tuning starts when
the controller is powered-on, the program is in STOP.
If SP-PV deviation is less than 0.3% f.s., Self-Tuning
switches to "one shot" Auto-Tuning; otherwise it calcu-
lates a point at 75% of deviation around which to start
"one shot" Auto-Tuning, considering a single Heat or
Cool action or a dual Heat/Cool action based on the
type of set control.
Example single action, PV less SP/4
First
Target
Set point
overshoot
Tune Target
Point
±1%f.s.
High Output
Zero Output
Low Output
Start
Self-Tuning
Example dual heat/cool action, PV greater than SP/4
Peak to
Peak
Target
Set point
High
Output
Zero
Output
Low
Output
A
A: Start of Autotune
Example with SP-PV deviation less than 0.3% f.s. dual
heat/cool action
Peak to
Peak
±2%f.s.
End
Self-Tuning
B
B: End of Autotune
145