4.25.5. RTD.LO - Calibrating minimum resistance value

Acronym
RTD.LO
The parameter appears if you are calibrating a custom I.MAIN RTD input.
To calibrate:
apply a resistance corresponding to minimum scale value to the main input (for example, 18.52 Ω for Pt100 ;
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-
4.25.6. RTD.HI - Calibrating maximum resistance value
Acronym
RTD.HI
The parameter appears if you are calibrating a custom I.MAIN RTD input.
To calibrate:
apply a resistance corresponding to maximum scale value to the main input (for example, 390.48 Ω for Pt100);
press the
key to acquire the calibration value.
Unit of measurement:
Options:
-
4.25.7. HOUR - Setting hours
Acronym
HOUR
The parameter shows and sets the hours on the Real Time Clock, if U.CAL = RTC.
Unit of measurement:
Options:
0...23
4.25.8. MIN - Setting minutes
Acronym
MIN
The parameter shows and sets the minutes on the Real Time Clock, if U.CAL = RTC.
Unit of measurement:
Options:
0...59
4.25.9. SEC - Setting seconds
80208G_MHW_650-1250-1350_01-2017_ENG
Scrolling message
-
Scrolling message
-
Scrolling message
-
Scrolling message
Hours
Scrolling message
Minutes
4. CONFIGURATION
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W
Submenu
Attributes
US.CAL
R W
133

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

12501350

Table of Contents