4.20.5. rES.t - Defining the timer reset command logic

Acronym
rES.t
LOGIC TYPE OF TIMER RESET
The parameter shows and sets the type of logic used to command the timer reset.
With positive logic, the timer is reset with "object" active.
With negative logic, the timer is reset with "object" inactive.
Unit of measurement:
Options:
POSIT
NEGAT = Negative logic
4.20.6. BAND - Band for timer count
Acronym
BAND
SYMM SP BAND WHERE TIMER IS ACTIVE
The parameter shows and sets the symmetrical band around the setpoint within which the timer count is on.
The parameter appears if the parameter F.tiM = STABL
If the parameter equals "0.0" the count is immediate as soon as the setpoint is reached for the first time.
Unit of measurement:
Options:
0.0...25.0
4.20.7. End - Selecting the function activated at end of count
Acronym
End
FUNCTION WHERE TIMER IS OVER
The parameter shows and sets the function that is activated when the timer ends the count.
The parameter appears if the parameter F.tiM = ST.STP or STABL.
Unit of measurement:
Options:
NONE
OFF
if the Multiset function is enabled:
SP1-2
4.20.8. TIMER - Timer value
Acronym
TIMER
ACTUAL TIME
The parameter shows and sets the timer value.
Unit of measurement:
Options:
0...9999
80208G_MHW_650-1250-1350_01-2017_ENG
Scrolling message
-
= Positive logic
Scrolling message
% of full scale of main input
Scrolling message
-
= None: control continues with actual setpoint
= Software off
= Change setpoint SP1/SP2
Scrolling message
Minutes or Seconds according to the selection set in the MODE submenu, parameter tMEr
4. CONFIGURATION
Submenu
Attributes
TIMER
R W
Submenu
Attributes
TIMER
R W
Submenu
Attributes
TIMER
R W
Submenu
Attributes
TIMER
R W
117