4.15.1. I.DIG.N - Selecting the digital input

Acronym
I.DIG.N
DIGITAL INPUT NUMBER
The parameter shows and sets the identifying number of the digital input to be configured.
Unit of measurement:
Options:
1...2
1...3
1...5
4.15.2. S.in.x - Defining the input state
Acronym
S.in.x
DIGITAL INPUT STATUS
The parameter shows and sets the state of the input with identifying number "x".
The direct digital input is active when there is current in the digital input or the contact is closed.
The inverse digital input is active when there is no current in the digital input or the contact is open.
Digital inputs can be forced so that they are always on or off.
Unit of measurement:
Options:
DIREC = Direct digital input
INVRS
OFF
ON
4.15.3. F.in.x - Selecting the assigned function
Acronym
F.in.x
DIGITAL INPUT FUNCTION
The parameter shows and sets the function assigned to the digital input with identifying number "x".
Unit of measurement: -
Options:
NONE
AU-MA
LO-RE
HOLD
AL.ACK
S.TUNE
A.TUNE
ON-OF
FKEY
WRI.EN
if the Multiset function is enabled:
SEL.L
SEL.H
if the Timer function is enabled:
T.STST
T.RST
if the Programmer function is enabled:
P.STST
P.STRT
P.STOP
P.RST
P.SKP
ST.SKP
ST.ENB
if the Logic Options function is enabled:
FB.IN
KEY.U
KEY.D
KEY.F
80208G_MHW_650-1250-1350_01-2017_ENG
Scrolling message
Number
for model 650 with 2 digital inputs option
for model 650 with 3 digital inputs option
for models 1250 and 1350 with 5 digital inputs option
Scrolling message
-
= Inverse digital input
= Digital input forced off
= Digital input forced on
Scrolling message
=
No assigned function
=
Automatic-Manual control
=
Local-Remote setpoint mode
=
Hold value of main input
=
Reset alarm latches
=
Activate Self-Tuning
=
Activate Auto-Tuning
=
Software ON-OFF
=
Block F key
=
Enable writing of configuration parameters
=
Select setpoint SETP1...SETP2 or SETP1...SETP4 low bit
=
Select set point SETP1...SETP4 high bit
SEL.L and SEL.H" have the meaning of selection Nr. program
=
START/STOP timer
=
RESET timer
=
START/STOP programmer base times
=
START programmer base times
=
STOP programmer base times
=
RESET programmer base times
=
SKIP to end of program (end cycle)
=
SKIP to end of step
=
STEP ENABLE: input with consent function at start of step
=
Function Blocks Input
=
replica UP button
=
replica DOWN button
=
replica F button