3. COMMISSIONING
3.4.2.
Setting up the Heater Break Alarm
If at least one output was configured as Heater Break Alarm in the fast configuration.
0000
Home page
0000
Press > 2 seconds
0
Enter password (default = 1) with the
PASS1
Press 4 times (if the model does not have remote setpoint input and current
transformer options and is not the Programmer)
AL.HB
Submenu
AL.HB
LOW.ON
THR.PE
LoAd
MSG.HB
0000
Home page
0000
The AL.HB submenu also lets you:
set an HB alarm due to low current draw (parameter
LOW.ON, default = 0.0);
set an HB alarm due to high current draw (parameter
HIG.ON, default = 0.0);
set an HB alarm due to excess current draw (parameter
HI.OFF, default = 0.0);
set the HB alarm trip delay (parameter TIME, default =
0);
select the control output assigned to the HB alarm
(parameter OUT, default = 1);
activate or deactivate flashing of the PV display in case
of alarm (parameter BLK.AL, default = OFF).
40
and
Press 4 times
Set the percentage of HB current compared to calibration (default = 80%) with the
keys. Description of parameter and list of options on page 82
Press twice
Select the connected load (default = MONO) with the
Description of parameter and list of options on page 82
Select the message assigned to the HB alarm (default = 0) with the
Description of parameter and list of options on page 82
Press > 2 seconds
keys
80208G_MHW_650-1250-1350_01-2017_ENG
and
keys
and
keys
and