Mitsubishi M80 series Connection And Set Up Manual page 69

Hide thumbs Also See for M80 series:
Table of Contents

Advertisement

M800S/M80 Series Connection and Setup Manual
4 General Specifications
(a) Skip signal input conditions
Use the input signal within the following condition ranges.
1
Input voltage at external contact ON
2
Input current at external contact ON
3
Input voltage at external contact OFF
4
Input current at external contact OFF
5
Input resistance
6
Input signal holding time (Ton)
7
Internal response time
8
Machine side contact capacity
Connection to 24V common
External signal
+24V
0V
Connection to 24V common
(Machine side)
SKIP
24VDC
0V(RG)
0V(RG)
COM
IB-1501269-F
Ton
2.35kΩ
2.35kΩ
Control
circuit
24V common
6V or less
6mA or more
20V or more, 25.2V or less
2mA or less
2.35kΩ
2ms or more
0.08ms or less
+30V or more, 16mA or more
Connection to 0V common
+24V
External signal
0V
Connection to 0V common
(Machine side)
SKIP
24VDC
COM
0V(RG)
32
0V common
18V or more, 25.2V or less
4V or less
Ton
2.35kΩ
2.35kΩ
Control
circuit