4 General Specifications
(Note 3) Always keep the total sum oftput current of each Y200 to Y207, Y208 to Y20F, Y210 to Y217,
Y 200
Y 201
Y 202
Y 203
Y 204
Y 205
Y 206
Y 207
Y 208
Y 209
Y 20A
Y 20B
Y 20C
Y 20D
Y 20E
Y 20F
Y 260
Y 261
Y 262
Y 263
Y 264
Y 265
Y 266
Y 267
Y 268
Y 269
Y 26A
Y 26B
Y 26C
Y 26D
Y 26E
Y 26F
CAUTION
1. When using an inductive load such as a relay, always connect a diode in parallel to the load to prevent a
counter-electromotive force.
2. When the rush current exceeds the maximum output current, always connect a protective resistor serially to
the load to suppress rush currents.
IB-1501269-F
Y218 to Y21F, Y220 to Y227, Y228 to Y22F, Y230 to Y237, Y238 to Y23F, Y260 to Y267, Y268
to Y26F, Y270 to Y277, and Y278 to Y27F less than 0.8A.
0.2A or less per point
Y210
Y211
Y212
Y213
Total 0.8A
Y214
or less
Y215
Y216
Y217
Y218
Y219
Y21A
Y21B
Total 0.8A
Y21C
or less
Y21D
Y21E
Y21F
0.2A or less per point
Y270
Y271
Y272
Y273
Total 0.8A
Y274
or less
Y275
Y276
Y277
Y278
Y279
Y27A
Y27B
Total 0.8A
Y27C
or less
Y27D
Y27E
Y27F
Total 1.9A or less
Y 220
Y 221
Y 222
Y 223
Total 0.8A
Y 224
or less
Y 225
Y 226
Y 227
Y 228
Y 229
Y 22A
Y 22B
Total 0.8A
Y 22C
or less
Y 22D
Y 22E
Y 22F
Total 3.8A or less
70
Y 230
Y 231
Y 232
Y 233
Total 0.8A
Y 234
or less
Y 235
Y 236
Y 237
Y 238
Y 239
Y 23A
Y 23B
Total 0.8A
Y 23C
or less
Y 23D
Y 23D
Y 23F