ABB i-bus
KNX
Commissioning
3.3.2.1.1

Output A,B: Blind - Drive parameter window

All settings for the blind drive are undertaken in this parameter window. It is visible if the Operation mode
parameter is set to Blind in the Output A,B Operation mode parameter window, p. 21.
Total travel time
in s [1...18,000]
Options:
This parameter defines the total travel time from the upper end position to the lower end position.
Slat adjustment switch on duration
in ms [30...65,535]
Options:
This parameter determines the switch on duration for slat adjustment, i.e. the time for which a slat is
rotated after it receives a STOP/Slat adjustment telegram.
Slat adjustment total travel time
[0...100] in ms [30...65,535]
Options:
This parameter determines the total travel time for slat adjustment, i.e. the time a slat requires to rotate
from one end position to the other.
Note
On larger slats there is a mechanical dead zone time involved until the blind reacts. For this reason,
the total slat travel time will be extended by this reaction time.
Reversing time delay in ms [50...5,000]
(see techn. data of the drive!)
Options:
This parameter defines the duration of the minimum reversing time between two directions of travel.
1...60...18,000
30...300...65,535
30...1,200...65,535
50...700...5,000
JRA/S 6.230.3.1 | 2CDC506083D0201 27