Output A Group Objects - ABB i-bus KNX JRA/S 6.230.3.1 Product Manual

Blind/roller shutter actuator with binary inputs
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.4.4.2

Output A group objects

No.
75
This group object is enabled if the Mode Output parameter is set to Switch actuator in the Output A, B: Mode parameter
window.
This group object switches the output ON/OFF. The device receives a Switch telegram via the Switch group object.
N/O:
Telegram value
N/C:
Telegram value
76
This group object is enabled if the Enable function Time parameter is set to Yes in the Output A,B: Switch actuator parameter
window.
If the communication object is assigned with the value 1, the output is switched on irrespective of the value of the
communication object Switch and remains switched on until the communication object Permanent ON has the value 0. When
the Permanent ON state ends, the state of the communication object Switch is used.
Permanent ON only switches ON and "masks" the other functions. This means that the other functions, e.g. Staircase lighting,
continue to run in the background but do not initiate a switching action. When permanent ON ends, the contact position which
would result without the permanent ON function becomes active. For the Staircase lighting function the reaction after
Permanent ON is parametrized in Output A,B: Switch actuator - Time parameter window, p. 42.
This communication object can be used, for example, to allow service or maintenance and cleaning personnel to initiate a
permanent ON. The device receives a switch telegram via the switch object.
Permanent ON becomes inactive after a download or bus voltage recovery.
Telegram value
106 2CDC506083D0201 | JRA/S 6.230.3.1
Function
Switch
1 = switch ON
0 = Switch OFF
1 = switch OFF
0 = Switch ON
Note
With logical connections or forced operations, a change in the Switch group object does not necessarily result in a
changed contact position.
For further information see: Function diagram, p. 126
Permanent on
1 = activates permanent ON mode
0 = Deactivates permanent ON mode
Object name
Output A
Output A
Data type
Flags
1 bit
C, W
DPT 1.001
1 bit
C, W
DPT 1.003