Output A,B: Blind - Safety parameter window

All settings for the Safety function are undertaken in this parameter window. It is visible if the Enable
function Safety parameter is enabled in Output A,B: Blind parameter window, p. 22.
Safety operation A active
This parameter is set to Yes.
36 2CDC506083D0201 | JRA/S 6.230.3.1
Activate safety operation
on object value
Options:
1
0
1: The safety operation is triggered by the value 1.
0: The safety operation is triggered by the value 0.
Position on safety operation
Options:
Unchanged
UP
DOWN
STOP
This parameter defines the reaction to the triggering of a safety operation.
Unchanged: The blind remains unchanged in its position and/or the current movement is
completed.
UP: The blind moves UP.
DOWN: The blind moves DOWN.
STOP: The output is electrically disconnected, i.e. a moving blind is stopped.