Staircase Lighting - ABB i-bus KNX JRA/S 6.230.3.1 Product Manual

Blind/roller shutter actuator with binary inputs
Table of Contents

Advertisement

®
ABB i-bus
KNX
Planning and application
4.2.2.1

Staircase lighting

After the staircase lighting time T
with the value 1 the time restarts (Retrigger function) unless the parameter Extending staircase lighting by
multiple switch on ("Pumping up") in the Output A,B: Switch actuator - Time parameter window, p. 42 is set
to No (not retriggerable).
This reaction is the basic reaction of the Staircase lighting function.
Via "pumping up" – operation of the push button several times in succession – users can adapt the
staircase lighting to current needs. The maximum duration of the staircase lighting time can be set in the
parameters.
If the device receives a further ON telegram while the staircase lighting is switched on, the staircase
lighting time is added to the remaining period.
128 2CDC506083D0201 | JRA/S 6.230.3.1