ABB i-bus
KNX
Commissioning
3.3.3.1

a: Blind sensor parameter window

This operation mode allows the operation of blinds and shutters with buttons or switches.
This parameter window is visible if the Blind sensor option is selected in the Input a Function parameter
window, p. 64.
Enable group object
"Block" 1-bit
Options:
Yes: The 1-bit group object Block is enabled. This can be used to disable the input.
Note
If the input is disabled and the option Send cyclically is set, the last state is still sent regardless of the
block. The Block option still blocks the physical input; sending continues internally.
Debounce time
Options:
Debouncing prevents unwanted multiple operations of the input, e.g. due to bouncing of the contact.
No
Yes
10/20/30/50/70/100/150 ms
JRA/S 6.230.3.1 | 2CDC506083D0201 65