Output A,B: Switch Actuator - Forced Operation Parameter Window - ABB i-bus KNX JRA/S 6.230.3.1 Product Manual

Blind/roller shutter actuator with binary inputs
Table of Contents

Advertisement

®
ABB i-bus
KNX
Commissioning
3.3.2.2.5

Output A,B: Switch actuator - Forced operation parameter window

All settings for the Forced Operation function are undertaken in this parameter window.
It is visible if the Enable function Forced operation parameter is enabled in Output A,B: Switch actuator
(only "UP" contact) parameter window, p. 38.
A Forced operation group object is available for every output.
The forced operation (a 1 bit or 2 bit communication object per output) sets the output in a defined state,
where – as long as the forced operation is active – it can only be changed via the communication object
forced operation.
The switch state after the end of forced operation can be set using the parameter Contact pos. if forced
operation.
Yes: The following parameters appear:
Type of object "Forced operation"
Options:
1-bit
2 bit
Using the 2-bit group object, the output state is defined directly via the group object value. Control
of the output via the Switch group object is disabled as long as the output is forcibly switched ON or
OFF.
JRA/S 6.230.3.1 | 2CDC506083D0201 55