Pulse Encoder Insulation (Acp600); Installation Of Optional Modules And Drive Window - ABB ACS 600 Series Hardware Manual

Table of Contents

Advertisement

Pulse Encoder
Insulation (ACP600)
Installation of
Optional Modules and
Drive Window
Placement
Power Supply
for the Module
Fiber Optic Link
ACS/ACC/ACP 604/607 Drives
The tachometer shall be insulated electrically from stator or rotor to
prevent forming of current path through the tachometer. The usual
coupling-type encoder must have an electrically insulating coupling.
When a hollow-shaft type tachometer is used, the insulation can be
implemented by insulating the ball joints of the engaging arm, or
insulating the bar of the engaging arm. Shield of the tachometer cable
should be insulated from the tachometer frame. The other end of the
shield is grounded at the converter drive.
This section gives general installation instructions for Drive Window PC
tool and ACx 600 optional modules, such as fieldbus adapters, I/O
extension modules and the pulse encoder interface. Connection
examples are given at the end of the section.
The module should be installed on the DIN mounting rail inside the
cabinet. Follow the instructions given in the Mechanical Installation
chapter of the module manual.
The 24 V d.c. supply for one optional module is provided by the NIOC/
NIOCP board of the converter (NIOC: terminal X23, NIOCP: terminal
X4). The location of the NIOC/NIOCP board is shown in the
dimensional drawings ( Appendix B ).
Optional modules are connected via a DDCS fiber optic link to the
NAMC board or NDCO board (mounted on top of the NIOC board). The
terminals on the NAMC/NDCO board to which the cables are
connected are as follows:
Module Type
Fieldbus Adapter Modules
I/O Extension Modules
Pulse Encoder Interface Module
Double Pulse Encoder Interface
Module (for ACP 600 only)
Drive Window
* on NDCO board when NAMC-1 board is used
Observe color codes when installing fiber optic cables. Blue connectors
should go to blue terminals, and grey connectors to grey terminals.
In case multiple modules are installed on the same channel, they must
be connected in a ring.
Chapter 3 – Electrical Installation
Channel
CH0
CH1
CH2 with ACS 600
Standard Application
Program 5.0
CH1 with ACC Application
Program
CH2
CH3
ACx=ACS/ACC/ACP
Terminals
V13*, V14*
V15, V16
V17, V18
V15, V16
V17, V18
V19, V20
3-9