Commissioning
3.4.3.1

group objects Switch sensor

No.
10
This group object is enabled if the Enable group object "Block" 1 bit parameter is set to Yes in the Input a: Switch sensor
parameter window.
Using the communication object Block, the input can be blocked or enabled. With activated communication object Block the
inputs are blocked.
Telegram value:
11
This group object is enabled if the Function parameter is set to Switch sensor in the Input a: Function parameter window and
the "Switch 1" parameter is set to Yes in the Input a: Objects "Switch" parameter window.
In accordance with the parameter setting, this group object can be switched by actuating the input to ON, OFF or TOGGLE or
can be set to No reaction. With toggle the previous value, e.g. 1, is toggled directly to the value 0. The group object can be
sent cyclically, e.g. for sensor lifesign monitoring.
Telegram value:
12
13
See communication object 46.
14
This group object is enabled if the "Start event 0/1" 1 bit parameter is set to Yes in the Input a: Switch sensor parameter
window.
The 1-bit communication object Start event 0/1 is enabled. As a result, the same events, except those of the push
button/switch connected to the binary input, can also be triggered by the receipt of a telegram on the communication object
Start event 0/1.
Telegram value:
100 2CDC506083D0201 | JRA/S 6.230.3.1
Function
Block
Note
When the input is blocked there is fundamentally no reaction to a signal change on the input, but:
– Waiting for a long button operation or a minimum signal duration is suspended.
– Parametrized Cyclic sending is not interrupted.
– It is still possible to write the Switch x group object.
If the input state changed during the blocked phase, this leads to immediate sending of the new communication
object value after enabling. If the input state remains the same during the blocking phase, the communication object
value is not sent.
0 = enable input a
1 = Block input a
Switch 1
Note
The communication object can be written to externally. Thus cyclic sending is interrupted or may not be possible
depending on the parameter setting.
No further group objects are visible with the setting.
0 = OFF
1 = ON
Switch 2
Switch 3
Start event 0/1
0 = start event 0
1 = Start event 1
Object name
Input a: Switch sensor
Input a: Switch sensor
Input a: Switch sensor
Data type
Flags
1 bit
C, W
DPT 1.003
1 bit
C, W, T
DPT 1.001
1 bit
C, W
DPT 1.001