Lamp Load Output 6 A - ABB i-bus KNX JRA/S 6.230.3.1 Product Manual

Blind/roller shutter actuator with binary inputs
Table of Contents

Advertisement

®
ABB i-bus
KNX
Device technology
Lamp load output 6 A
2.1.3
Lamps
Fluorescent lamps T5/T8
Low-voltage halogen lamps
Dulux lamp
Mercury-vapor lamp
Switching capacity (switching contact)
Device type
Application
JRA/S 6.230.3.1
Shutter Actuator binary input 6f12f/...
* ... = Current version number of the application. Please refer to the software information on our website for this purpose.
Note
ETS and the current version of the device application are required for programming.
The current version of the application is available for download at www.abb.com/knx. After import into
ETS, it is available in ETS under ABB/Blind/Switch.
The device does not support the locking function of a KNX device in ETS. Using a BCU code to inhibit
access to all the project devices has no effect on this device. Data can still be read and programmed.
10 2CDC506083D0201 | JRA/S 6.230.3.1
Incandescent lamp load
Uncompensated
Parallel compensated
DUO circuit
Inductive transformer
Electronic transformer
Halogen lamps 230 V
Uncompensated
Parallel compensated
Uncompensated
Parallel compensated
Maximum peak inrush current I
p
Maximum peak inrush current I
p
Maximum peak inrush current I
p
Max. number of
Group objects
255
1200 W
800 W
300 W
350 W
800 W
1000 W
1000 W
800 W
800 W
1000 W
800 W
(150 µs)
200 A
(250 µs)
160 A
(600 µs)
100 A
Max. number of
Group addresses
255
Max. number of
assignments
255