Commissioning; Supplied State; Overview; Input Functions - ABB i-bus KNX JRA/S 6.230.3.1 Product Manual

Blind/roller shutter actuator with binary inputs
Table of Contents

Advertisement

®
ABB i-bus
KNX

Commissioning

3
Commissioning
3.1

Supplied state

In the supplied state, all outputs are set to Blind mode.
All inputs are set to 2-button blind operation mode, with the first input assigned to "up" and the second to
"down".
Input pairs are always assigned to the output with the same letter (e.g. a, b to A, B)
This means that the outputs can be switched as soon as the bus voltage is applied:
Closing the contact at input a closes relay A, raising the connected blind. Closing the contact at input b
closes relay B, lowering the connected blind.
3.2

Overview

The Shutter Actuator binary input 6f12f application and ETS Engineering Tool Software 4.2 or later are
used to parametrize the device. The application provides the device with a comprehensive and flexible
range of functions. The standard settings allow simple commissioning. The functions can be expanded
if required.
The available functions are as follows:
Binary input
Blind/shutter
3.2.1

Input functions

The following table provides an overview of the functions possible with the device inputs and the
Shutter Actuator binary input 6f12f application:
Input functions
Switch sensor
Switch/dimming sensor
Blind sensor
Value/forced operation
 = Function is supported
Twelve binary inputs are available, e.g. Light ON/OFF in the entrance area of the
room, in the bathroom and for freestanding or table lamps, move blinds UP/DOWN,
and send an emergency signal.
Six blind outputs are available. They can also be set as switch outputs.
a...l
JRA/S 6.230.3.1 | 2CDC506083D0201 15