Blind sensor group objects

No.
10
This group object is enabled if the Enable group object "Block" 1 bit parameter is set to Yes in the Input a: Blind sensor
parameter window.
Using the communication object Block, the input can be blocked or enabled. With activated communication object Block the
inputs are blocked.
Telegram value:
11
This group object is enabled if the Function parameter is set to Blind sensor in the Input a: Function parameter window.
This group object sends a blind UP or DOWN Move telegram on the bus. By receiving telegrams, the device also recognizes
Move telegrams from another sensor, e.g. parallel operation.
Telegram value
12
This group object is enabled if the Function parameter is set to Blind sensor in the Input a: Function parameter window.
This communication object sends a STOP telegram or slat adjustment.
Telegram value
102 2CDC506083D0201 | JRA/S 6.230.3.1
Function
Block
Note
When the input is blocked there is fundamentally no reaction to a signal change, but:
– Waiting for a long button operation or a minimum signal duration is suspended.
– Parametrized Cyclic sending is interrupted.
– Group objects continue to be updated and sent if necessary.
When enabling an input, a change of the signal states (as opposed to before the block) leads to immediate
processing, e.g.:
– The minimum actuation or detection of a long/short button push starts.
– Group objects send their current value if necessary.
0 = enable input a
1 = Block input a
Blind UP/DOWN
0 = UP
1 = DOWN
STOP/slat adjustment
0 = STOP/slat adjustment UP
1 = STOP/slat adjustment DOWN
Object name
Input a:
Blind sensor
Input a:
Blind sensor
Input a:
Blind sensor
Data type
Flags
1 bit
C, W
DPT 1.003
1 bit
C, W, T
DPT 1.008
1 bit
C, T
DPT 1.007