Output A,B: Switch actuator - Time parameter window

All settings for the Time function – Staircase lighting, Switching ON/OFF delay and Flashing – are
undertaken in this parameter window.
This parameter window is visible if the Enable function Time parameter is enabled in Output A,B: Switch
actuator (only "UP" contact) parameter window, p. 38.
Explanations of the Time functions and sequences are provided in Planning and application, p. 115.
Please also observe Function diagram, p. 126, from which the switching and timing priorities originate.
Note
Observe the contact life span and switching cycles per minute.
For the contact life and switching operations per minute, see Technical data, p 7
Time function
Options:
This parameter defines the type of Time function for each output.
Staircase lighting: The value that switches the staircase lighting on and off can be parametrized.
The staircase lighting time starts when the function is switched on. It is switched off immediately after
the staircase lighting time ends.
Note
The Staircase lighting function can also be called via the Switch, Logical connection x (x = 1, 2) group
object or with a light scene recall.
Switching ON/OFF delay: The output can be switched on or off with a delay via this function.
Flashing: see Output A,B: Switch actuator - Time, - Flashing parameter window, p. 47.
42 2CDC506083D0201 | JRA/S 6.230.3.1
Staircase lighting
Switching ON/OFF delay
Flashing