Planning and application
4.2.2.2

Switching ON/OFF delay

The ON/OFF delay delays output switch-on or switch-off.
The delay time T
telegram.
If a new ON telegram with the value 1 is received during the switching ON delay, the delay time starts
again. The same applies to the switching OFF delay if a new OFF telegram with the value 0 is received.
Note
If the device receives an OFF telegram during the switching on delay T
disregarded.
or T
starts after a Switch telegram; once it has elapsed, the output executes the
D1
D0
, ON telegrams are
D1