Setting The Pmu Station Communication (Pmu Configuration) - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 11
Establishing connection and verifying the IEEE C37.118/1344 communication
11.3
102
Setting the PMU station communication (PMU
configuration)
To enable IEEE C37.118/1344 communication, the corresponding OEM ports must
be activated. The galvanic Ethernet front port and the rear optical ports can be used
for IEEE C37.118/1344 communication.
To enable IEEE C37.118/1344 synchrophasor communication:
1.
Enable communication for by navigating to: Main menu/Configuration/
Communication/Ethernet configuration.
1.1. Select the port.
1.2. Set values for Mode, IPAddress and IPMask. Mode must be set to
Normal.
1.3. Check that the correct IP address is assigned to the port.
2.
Set the TCP communication parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Configuration/PMUCONF. The first three parameters
are related to TCP communication. The default TCP parameters setting can
be used. More information regarding TCP communication is available in the
Application manual under section Short guidance for use of TCP.
3.
Set the UDP communication parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Configuration/PMUCONF. The first three parameters
are related to TCP communication and the rest of parameters are related to
setting of six independent UDP client groups. Each UDP group has eight
parameters. More information regarding UDP communication is available in
the Application manual under section Short guidance for use of UDP. The
following steps describes setting parameters for the first UDP group:
3.1. Enable the first UDP group by setting the parameter SendDataUDP1 to
On.
3.2. Set the UDP client IP address by setting the parameter
UDPDestAddres1 to 192.168.1.99. For the purpose of the
communication set-up in this section the LAN IP address of the PC is
used, where the PDC client tool is installed.
3.3. The default parameter settings can be used for the rest of parameters for
the first UDP group.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 073-UEN A
GUID-B4BA9F74-5E28-42FC-8F33-0BC98D5AE6B0 v2
Commissioning manual