1MRK 505 339-UEN B
Section 8
8.1
Overview
The rear OEM ports are used for:
•
process bus (IEC 61850-9-2LE) communication
•
substation bus (IEC 61850-8-1) communication.
For IEC 61850-8-1 redundant communication, both rear OEM ports are utilized. In this case IEC
61850-9-2LE communication can not be used.
8.2
Setting the station communication
To enable IEC 61850 communication the corresponding OEM ports must be activated. The rear
OEM port AB and CD is used for IEC 61850-8-1 communication. For IEC 61850-8-1 redundant
communication, both OEM port AB and CD are used exclusively.
To enable IEC 61850 station communication:
1.
Enable IEC 61850-8-1 (substation bus) communication for port AB.
1.1.
1.2.
2.
Enable redundant IEC 61850-8-1 communication for port AB and CD
2.1.
Commissioning manual
Establishing connection and
verifying the IEC 61850
communication
IEC 61850-9-2LE process bus communication is not supported in the IED.
Set values for the rear ports AB.
Navigate to: Main menu/Configuration/Communication/Ethernet configuration/
LANAB:1
Mode , IPAddress and IPMask . Mode must be set to Normal .
Set values for
Check that the correct IP address is assigned to the port.
Enable IEC 61850-8-1 communication.
Navigate to: Main menu/Configuration/Communication/Station communication/
IEC61850-8-1/IEC61850–8–1:1
Operation to On , PortSelGOOSE and PortSelMMS to the port used (for example
Set
LANAB ).
Enable redundant communication.
Navigate to: Main menu/Configuration/Communication/Ethernet configuration/
PRP:1
Operation , IPAddress and IPMask . Operation must be set to On .
Set values for
The IED will restart after confirmation. Menu items LANAB:1 and LANCD:1 are
hidden in local HMI after restart but are visible in PST where the values for
Mode is set to Duo .
parameter
Establishing connection and verifying the IEC 61850 communication
Section 8
SEMOD172103-4 v6
SEMOD172108-3 v10
57