Using Front-Connected Pc - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UEN A
16.2.2
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Commissioning manual
HMI Signal Name:
Status
RTC
READY / FAIL
Time Sync
READY / FAIL
Application
READY / FAIL
RTE
READY / FAIL
IEC61850
READY / FAIL
LMD
READY / FAIL
LDCMxxx
READY / FAIL
OEM
READY / FAIL
Also the internal signals, such as INT--FAIL and INT--WARNING can be
connected to binary output contacts for signalling to a control room.
In the IED Status - Information, the present information from the self-supervision
function can be viewed. Indications of failure or warnings for each hardware
module are provided, as well as information about the external time
synchronization and the internal clock. All according to table 26. Loss of time
synchronization can be considered as a warning only. The IED has full
functionality without time synchronization.

Using front-connected PC

When an internal fault has occurred, extensive information about the fault can be
retrieved from the list of internal events available in the SMS part:
TRM-STAT TermStatus - Internal Events
The list of internal events provides valuable information, which can be used during
commissioning and fault tracing.
The internal events are time tagged with a resolution of 1ms and stored in a list.
The list can store up to 40 events. The list is based on the FIFO principle, when it is
Troubleshooting
Description
This signal will be active when there is a
hardware error with the real time clock.
This signal will be active when the
source of the time synchronization is
lost, or when the time system has to
make a time reset.
This signal will be active if one or more
of the application threads are not in the
state that Runtime Engine expects. The
states can be CREATED, INITIALIZED,
RUNNING, etc.
This signal will be active if the Runtime
Engine failed to do some actions with the
application threads. The actions can be
loading of settings or parameters for
components, changing of setting groups,
loading or unloading of application
threads.
This signal will be active if the IEC 61850
stack did not succeed in some actions
like reading IEC 61850 configuration,
startup etc.
LON network interface, MIP/DPS, is in
an unrecoverable error state.
Line Differential Communication Error
status
Optical Ethernet Module error status
Section 16
M11763-203 v5
279