ABB REG670 Commissioning Manual page 143

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UEN A
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Commissioning manual
Testing functionality by secondary injection
11
X1Zx
10
40% of RLdFw
80% of RLdFw
IEC05000368 V4 EN-US
Figure 42:
Distance protection characteristic with test points for phase-to-
phase measurements
Table 19:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPPZx x tan (ArgLd)
R
0.85 x RFPPZx
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
0
R
RLdFw
8
X
–0.2143 x RFPPZx/2
R
0.8 x RFPPZx/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
Table continues on next page
X
2
1
80%
3
50%
4
12
120°
a
5
6
R (Ohm/phase)
7
13
9
c
20°
8
0.5 x RFPPZx
IEC05000368-4-en.vsdx
set
set
set
set
+ RFPPZx/2
set
set
+ RFPPZx/2
set
set
set
Section 13
Comments
ArgLd = angle for the maximal load
transfer
Exact: 0.8 x RFPPZx/2 (ArgDir=20°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
137