Measuring The Operating Limit Of Set Values - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UEN A
13.4.2.1
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Commissioning manual
Testing functionality by secondary injection
Test point
Reach
Value
4
X
R
5
X
R
6
X
R
7
X
R
8
X
R
9
X
R
10
X
R
11
X
R
12
X
R
13
X
R

Measuring the operating limit of set values

Procedure:
1.
Subject the IED to healthy normal load conditions for at least two seconds.
2.
Apply the fault condition and slowly decrease the measured impedance to
find the operating value of the phase-to-phase fault for zone 1 according to
test point 1 in figure
with the set value.
3.
Repeat steps
1
to
2
Observe that the zones that are not tested have to be blocked and the zone that
is tested has to be released.
4.
Repeat steps
1
to
3
E according to figure
0.5 x (2 x X1
+ R0
)/3
set
set
0.5 x (2 x R1
+R0
)/3 +
set
set
RFPEZx
set
0.85 x RFPEZx
x tan(ArgLdset)
set
0.85 x RFPEZx
RLdFwset x tan(ArgLdSet)
RLdFw
set
0
RLdFw
set
–02143 x RLdFw
set
0.8 x RLdFw
set
–0.8 x RLdFw
x tan(ArgDir=20°)
set
–0.8 x RLdFwd
x
set
tan(ArgDir=20°)
0.8 x RLdFw
set
0.17 x (2 x X1
+ X0
)
set
set
-0.36 x (2 x X1
+ X0
)
set
set
0.27 x (2 x X1
+X0
)
set
set
–0.57 x (2 x X1
+ X0
)
set
set
0.5 x (2 x X1
+ X0
)/3
set
set
0.5 x (2 x R1
+ R0
)/3
set
set
0
RFPEZx
42
and table 19. Compare the result of the measurement
to find the operating value for test points 2, 3 in table
to find the operating value for the phase-to-earth fault L3-
43
and table 20.
Section 13
Comments
ArgLd = angle for the maximal load
transfer
Exact: 0.8 x RFPEZx x tan
(ArgDir=20°)
Exact: 0.5 x (2 x X1
X0
)/3
set
set
Exact: 0.5 x (2X1
+ X0
)/(3 x
set
set
tan(AgNegDir=30°)
Exact: 0.8 x (2 x X1
+ X0
set
set
Exact: 0.8 x (2X1set + X0set)/(3 x
tan(AgNegDir=30°)
GUID-3FA4B640-38E7-406E-8FCC-8DEDABB024C4 v4
)/3
19
139