Optical budget calculation for PMU - PDC
communication
Most of the times, the PMU IEDs are located in the substations. A local PDC might
be located in the substation. For communications within the substation or between
the IED and the WAN/LAN access point, it is important to know what is the optical
budget available. The graph in Figure
PMU – PDC configuration using typical OEMs.
14
12
62.5/125 µm
10
8
6
50/125 µm
4
2
0
0
0.5
1.0
1.5
FIBER OPTIC CABLE LENGTH - km
IEC11000409 V1 EN-US
Figure 38:
Optical power budget for fiber optic cable lengths
As shown in the graph, if one uses a 62.5/125 µm fiber, the value under the
62.5/125 µm curve represents the remaining optical budget at any link length,
which is available for overcoming non-fiber cable related losses.
Losses in the connectors and splices are typically 0.3dB/connection. The user must
reserve 3dB spare for the uncertainty of the measurements.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
38
shows the dynamic range available for a
2.0
2.5
3.0
3.5
4.0
IEC11000409_1_en.vsd
1MRK 502 073-UEN A
GUID-F5DEACB1-4B83-4C68-B59A-694CAC78AF3D v3