ABB REG670 Commissioning Manual page 111

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UEN A
Establishing connection and verifying the IEEE C37.118/1344 communication
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Commissioning manual
IEEE1344 communication, the 1344TCPport parameter setting can be
used (4713 is default).
2.3. Set the Protocol as IEEE C37.118.2-2011.
2.4. Set the Device ID Code in PMU Connection Tester per PMU Data
Stream ID Number (IDCODE). The PMU Data Stream ID Number is a
user assigned ID number (1-65534) for each data stream sent out from
the PMU and it is defined under parameter PMUdataStreamIDCODE.
(Main menu/Configuration/Communication/Station
communication/phasor measurement/PMU Report/PMUREPORT:
1)
2.5. Make sure that the Configure Alternate Command Channel is set as Not
Defined. The Configure Alternate Command Channel is used to
configure a TCP channel to control the UDP data communication and
transfer the header, configuration and command frames.
2.6. Continue to the section
communication.
3.
Set the Connection Parameters on PMU Connection Tester for UDP
communication according to the PMU configuration.
IEC140000136 V1 EN-US
3.1. Set the Local Port to UDP destination port defined in the PMU under
the parameter UDPDestPort1 (Default value: 8910).
3.2. Click the Configure Alternate Command Channel to configure the
TCP channel. A new window will pop up. A TCP channel needs to be
configured in order to control the UDP data communicatiuon and
transfer the header, configuration and command frames.
Verifying the IEEE C37.118/1344 TCP
Section 11
IEC140000136-1-en.vsd
105

Advertisement

Table of Contents
loading

Table of Contents