Measuring The Operate And Time Limit For Set Values - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

1MRK 502 073-UEN A
13.5.6.1
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
Commissioning manual
Testing functionality by secondary injection
IED test set
NI
L1U
L2U
L3U
NU
IEC09000021 V2 EN-US
Figure 54:
Principle connection of the test set
Values of the logical signals belonging to the sensitive directional residual
overcurrent and power protection are available on the local HMI under Main
menu/Test/Function status/Current protection/SensDirResOvCurr(67N,IN>)/
SDEPSDE(67N,IN>):x

Measuring the operate and time limit for set values

Operation mode 3I
0
Procedure
1.
Set the polarizing voltage to 1.2 · UNRel> and set the phase angle between
voltage and current to the set characteristic angle (RCADir). Note that the the
current lagging the voltage.
Take setting RCAComp into consideration if not equal to 0.
2.
Inject current until the function picks up, and make sure that the operate
current of the set directional element is equal to the INcosPhi> setting.
The I Dir (3I
· cosφ) function activates the START and STDIRIN output.
0
3.
Assume that φ´ is the phase angle between injected voltage (3U
(3I
) i.e. φ´ = RCADir-φ. Change φ´ to for example 45 degrees. Increase the
0
injected current until the function operates.
4.
Compare the result with the set value and make sure that the new injected 3I
· cos φ is equal to the setting INcosPhi>..
Take the set characteristic into consideration, see Figure
NI
U1
U2
U3
NU
TRIP
IEC09000021-2-en.vsd
· cosφ
Section 13
IED
) and current
0
55
and Figure 56.
SEMOD175060-12 v2
SEMOD175060-34 v9
0
181