Calibrating injection based 100% stator earth fault protection
80
Clicking the Submit button, the result is stored for later calculations. ICT
automatically shifts to the second calibration sub tab, Step2: Calibration
step 2.
GUID-3C7F0567-2367-46E4-9606-FCFC7408DAA0 V1 EN-US
Figure 21:
ICT calibration tab 1 including the stability region indicator bar
5.
Connect a calibration resistance Rcal between the neutral point of the
generator and ground; the value of the calibration resistance can be selected
on the basis of the impedance to ground of the stator:
£
£ ×
Z
R
2
Z
stat
cal
IECEQUATION17022 V1 EN-US
The stator impedance to ground can be estimated by one of the below
quantities:
The total impedance to ground of the stator windings at the injection
frequency:
1
=
Z
stat
1
+
w
j C
R
N
IECEQUATION17023 V1 EN-US
where R
is the primary grounding resistor
N
The total impedance to ground of the stator windings at the injection
frequency taking into account the equivalent resistance R
grounding resistor transferred to the primary side of the grounding
transformer:
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
stat
stat
1MRK 502 073-UEN A
Stability region
indicator bar
IEC11000047-1-en.vsd
,eq of the
N
Commissioning manual