Verifying Settings - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
13.6.6.2
214
DU
=
Beta
U
3 N
EQUATION2072 V2 EN-US
considering stated accuracy (beta is a setting parameter)
4.
Increase the voltage U
voltage U
to zero and measure the time delay for the activation of the
3N
signals TRIP and TRIP3H.
The 100% stator earth fault protection also has a fundamental frequency
neutral point overvoltage function (95% stator earth fault protection). This
part of the protection can be tested separately by means of fundamental
frequency voltage injection from a test equipment.

Verifying settings

1.
With the generator rotating at rated speed but not connected: check the value
of the following analogue signals: E3 (the magnitude of the 3
induced voltage in the stator), U
voltage measured at the neutral side of the generator), U
the third-harmonic voltage measured at the terminal side of the generator) and
ANGLE (the angle between the third-harmonic voltage phasors U
U
). The value of E3 should be close to the following value:
3T
(
=
-
E3
U
U
3 N
3T
EQUATION2076 V1 EN-US
Make sure that ANGLE has a value bigger than 125°
2.
Read the value of DU (differential voltage). The value of DU should be close
to the following value:
(
=
+
DU
U
U
3 N
EQUATION2078 V1 EN-US
3.
Read the value of BU (bias voltage: Beta ·U
well below 1 for a non-faulted generator.
4.
After synchronization of the generator the ratio DU/BU is checked for
different load levels of the generator. These different monitoring of load
levels should be the base for the setting of beta.
If the function is used with the option of neutral point measurement only the
test is performed by check of this voltage. The operate value should be above
the measured residual third-harmonic voltage in the neutral point at normal
operation (non-faulted generator).
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
so that the sart signal falls. After that, switch the
3N
(the magnitude of the third-harmonic
3N
) (
2
×
+
cos(ANGLE)
U
3T
) (
2
×
+
cos(ANGLE)
U
3T
1MRK 502 073-UEN A
rd
harmonic
(the magnitude of
3T
3N
)
2
×
sin(ANGLE)
)
2
×
sin(ANGLE)
3T
). The ratio DU/BU should be
3N
Commissioning manual
(Equation 102)
SEMOD158990-144 v3
and
(Equation 103)
(Equation 104)