Setting The Pmu Station Communication (Pmu Configuration) - ABB RED670 Commissioning Manual

Relion 670 series, line differential protection
Hide thumbs Also See for RED670:
Table of Contents

Advertisement

Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
9.3
74
Setting the PMU station communication (PMU
configuration)
To enable IEEE C37.118/1344 communication, the corresponding OEM ports must
be activated. The galvanic Ethernet front port and the rear optical ports can be used
for IEEE C37.118/1344 communication.
To enable IEEE C37.118/1344 synchrophasor communication:
1.
Enable communication for by navigating to: Main menu/Configuration/
Communication/Ethernet configuration.
1.1. Select the port.
1.2. Set values for Mode, IPAddress and IPMask. Mode must be set to
Normal.
1.3. Check that the correct IP address is assigned to the port.
2.
Set the TCP communication parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Configuration/PMUCONF. The first three parameters
are related to TCP communication. The default TCP parameters setting can
be used. More information regarding TCP communication is available in the
Application manual under section Short guidance for use of TCP.
3.
Set the UDP communication parameters by navigating to: Main menu/
Configuration/Communication/Station communication/phasor
measurement/PMU Configuration/PMUCONF. The first three parameters
are related to TCP communication and the rest of parameters are related to
setting of six independent UDP client groups. Each UDP group has eight
parameters. More information regarding UDP communication is available in
the Application manual under section Short guidance for use of UDP. The
following steps describes setting parameters for the first UDP group:
3.1. Enable the first UDP group by setting the parameter SendDataUDP1 to
On.
3.2. Set the UDP client IP address by setting the parameter
UDPDestAddres1 to 192.168.1.99. For the purpose of the
communication set-up in this section the LAN IP address of the PC is
used, where the PDC client tool is installed.
3.3. The default parameter settings can be used for the rest of parameters for
the first UDP group.
1MRK 505 378-UEN A
GUID-B4BA9F74-5E28-42FC-8F33-0BC98D5AE6B0 v2
Line differential protection RED670 2.2 IEC
Commissioning manual

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents