Overcurrent Feature With Current Restraint; Overcurrent Feature With Voltage Restraint; Overcurrent Feature With Directionality - ABB REG670 Commissioning Manual

Generator protection, relion 670 series
Hide thumbs Also See for REG670:
Table of Contents

Advertisement

Section 13
Testing functionality by secondary injection
13.8.1.2
13.8.1.3
13.8.1.4
222

Overcurrent feature with current restraint

The current restraining value has also to be measured or calculated and the
influence on the operation has to be calculated when the testing of the operate
value is done.
Procedure
1.
Operate value measurement
The current restraining value has also to be measured or calculated and the
influence on the operation has to be calculated when the testing of the operate
value is done.

Overcurrent feature with voltage restraint

Procedure
1.
Connect the test set for injection of three-phase currents and three-phase
voltages to the appropriate current and voltage terminals of the IED.
2.
Inject current(s) and voltage(s) in a way that relevant measured (according to
setting parameter CurrentInput and VoltageInput) currents and voltages are
created from the test set.
Overall check in principal as above (non-directional overcurrent feature)
3.
Operate value measurement
The relevant voltage restraining value (according to setting parameter
VoltageInput) has also to be injected from the test set and the influence on the
operate value has to be calculated when testing of the operate value is done.
4.
Operate time measurement
Definite times may be tested as above (non-directional overcurrent feature).
For inverse time characteristics the START value (to which the overcurrent
ratio has to be calculated) is the actual pickup value as got with actual
restraining from the voltage restraining quantity.

Overcurrent feature with directionality

Please note that the directional characteristic can be set in two different ways either
just dependent on the angle between current and polarizing voltage (setting
parameter DirPrinc_OC1 or DirPrinc_OC2 set to or in a way that the operate
value also is dependent on the angle between current and polarizing voltage
according to the I · cos(F) law (setting parameter DirPrinc_OC1 or DirPrinc_OC2
set to I · cos(F). This has to be known if a more detailed measurement of the
directional characteristic is made, than the one described below.
Procedure
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 073-UEN A
SEMOD56488-35 v3
SEMOD56488-44 v5
SEMOD56488-60 v5
Commissioning manual

Advertisement

Table of Contents
loading

Table of Contents