Section 13
Testing functionality by secondary injection
142
Table 21:
Test points for phase-to-phase loops L1-L2 (Ohm/Loop)
Test point
Reach
Set value
1
X
X1
R
0
2
X
X1
R
R1
3
X
0.8 x X1
R
0.8 x R1
4
X
0.5 x X1
R
0.5 x R1
5
X
0.85 x RFPPZx x tan (ArgLd)
R
0.85 x RFPPZx
6
X
RLdFw x tan (ArgLd)
R
RLdFw
7
X
RLdFw x tan (ArgLd)
R
0
8
X
–0.2143 x RFPPZx/2
R
0.8 x RFPPZx/2
9
X
–0.4 x RLdFw x tan(ArgDir=20°)
R
0.4 x RLdFw
10
X
0.5 x X1
R
–0.23 x X1
11
X
0.8 x X1
R
–0.37 x X1
12
X
0.5 x X1
R
0.5 x R1
13
X
0
R
0.5 x RFPPZx
Table
21
is used in conjunction with figure 44.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
set
set
set
set
+ RFPPZx/2
set
set
+ RFPPZx/2
set
set
set
set
set
set
set
1MRK 502 073-UEN A
Comments
ArgLd = angle for the maximal load
transfer
Exact: 0.8 x RFPPZx/2
(ArgDir=20°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Exact –0.5 x R1
x
set
tan(ArgNegRes=30°)
Commissioning manual