Section 13
Testing functionality by secondary injection
13.16.1.2
13.17
266

Completing the test

Continue to test another function or end the test by changing the TESTMODE
setting to Off. Restore connections and settings to their original values, if they were
changed for testing purposes.

Exit test mode

The following procedure is used to return to normal operation.
After exiting the IED test mode, make sure that the MU is returned
to normal mode.
1.
Navigate to the test mode folder.
2.
Change the On setting to Off. Press the 'E' key and the left arrow key.
3.
Answer YES, press the 'E' key and exit the menus.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
1MRK 502 073-UEN A
M11369-39 v4
SEMOD53244-3 v5
Commissioning manual