Section 13
Testing functionality by secondary injection
150
If the rated secondary current I
current test I
is
ts
I
I
4
I
4
A
= ×
=
ts
ovrl
rs
EQUATION14041 V1 EN-US
If the CT of the generator has ratio 9000/1 A, then in primary values
I
rp
I
I
I
4
=
×
= ×
t
ovrl p
,
ovrl
I
rs
EQUATION14042 V1 EN-US
Reference is made to the numerical values of the example, explained in the
"Setting guidelines" of the Application Manual. A test current equal to 2.5 time the
base current of the generator is chosen; this choice is related to the selected test
voltage that is applied while testing the point SE and RE.
I
2 5
.
I
2 5 8367 20918
.
=
×
=
×
t
Base
EQUATION14043 V1 EN-US
The parameter ReachZ1 defines the boundary between zone 1 and zone 2; it is
expressed in percent of the parameter ForwardX. If the setting of ReachZ1 = 12%,
then corresponding primary value of the reactance is
ReachZ
1
ForwardX
X
=
×
RZ 1
100
100
EQUATION14044 V1 EN-US
The calculation of the test voltage, that is related to ReachZ1, is based on the
impedance Z
that has imaginary part X
RZ1
Re
achZ
1
ForwardR
RRZ
1
=
×
100
100
EQUATION14045 V1 EN-US
The magnitude of the impedance Z
=
2
+
2
=
Z
R
X
RZ
1
RZ
1
RZ
1
EQUATION14046 V1 EN-US
Hence the reference voltage of the test of the boundary between zone 1 and zone 2
is
V
Z
I
0 069 20918 1435
.
=
×
=
×
t RZ
,
1
RZ
1
t
EQUATION14047 V1 EN-US
If the test voltage is lower than V
the zone 1; if the test voltage is higher than V
zone 2.
Generator protection REG670 2.2 IEC and Injection equipment REX060, REX061, REX062
of the analog channel is 1 A, then the maximum
rs
9000
36000
A
=
1
A
=
12
59 33
.
ZBase
×
=
×
100
100
and real part R
RZ1
12
8 19
.
ZBase
×
=
×
100
100
is:
RZ1
2
+
2
=
W
0.009
0.068
0.069
V
=
(or in opposition), then the test is related to
t,RZ1
t,RZ1
1MRK 502 073-UEN A
0 9522 0
.
.0 0 68Ω
×
=
:
RZ1
0 9522 0 0
.
. 0 0 9Ω
×
=
, then the test is related to the
Commissioning manual
(Equation 1)
(Equation 2)
(Equation 3)
(Equation 4)
(Equation 5)
(Equation 6)
(Equation 7)