S3 Logic Inputs

User Inputs

USER INPUT A
Press [ ] for more
GE Multilin
PATH: SETPOINTS
S3 LOGIC INPUTS
USER INPUT A NAME:
User Input A
USER INPUT A SOURCE:
MESSAGE
Disabled
USER INPUT A
MESSAGE
FUNCTION: Disabled
USER INPUT A
MESSAGE
RELAYS (3-7): -----
USER INPUT A
MESSAGE
DELAY:
There are twenty (20) general purpose user input functions (User Inputs A through
T) that generate outputs in response to an asserted logic input. These functions can
be used to: initiate a trip; initiate a trip and a reclosure (760 only); log a contact
operation in the event recorder; convert an external contact into a self-resetting,
latched or pulsed contact.; convert an external contact into a Form-C contact; and
provide a contact multiplier for an external contact by operating multiple relays.
The setpoints for User Input A are shown above; setpoints for User Inputs B through
T are identical.
http://www.GEmultilin.com
Feeder Management Relay
USER INPUTS
USER INPUT A(T)
Range: 18 alphanumeric characters
Range: Input 1 to Input 20, Disabled
Range: Disabled, Trip, Trip & AR,
Alarm, Latched Alarm, Control
Range: Any combination of 3 to 7
Auxiliary relays
Range: 0.00 to 600.00 s in steps of 0.01
0.00 s
750/760
5–23