10.5. Set the monitored contact to the closed state and the virtual input to the
on state. Check that the diagnostic message is removed from the display
with the Auxiliary LED and relay deactivated.
10.6. Repeat steps 10.3 through 10.5 for all functions programmed to be
asserted by a Open & Voff input.
11. For
INPUT ASSERTED LOGIC
11.1. Check that there is no logic input diagnostic message on the display.
11.2. Set the monitored contact for the logic input programmed in setpoint
message User Input A Source to the closed state and the virtual input to
the off state. Check that the diagnostic message, either User Input A or
the name programmed in setpoint User Input A Name, appears on the
display with the Auxiliary LED and relay activated. Check in the Event
Recorder that the selected function has been invoked.
11.3. Leave the monitored contact in the closed state and put the virtual input
in the on state. Check that the diagnostic message, the Auxiliary LED and
relay remain activated.
11.4. Set the monitored contact to the open state and leave the virtual input in
the on state. Check that the diagnostic message, the Auxiliary LED and
relay remain activated.
11.5. Leave the monitored contact in the open state and put the virtual input in
the off state. Check that the diagnostic message is removed from the dis-
play with the 3 Auxiliary LED and relay deactivated.
11.6. Repeat steps 11.3 through 11.5 for all functions programmed to be
asserted by a Closed | Von input.
12. For
INPUT ASSERTED LOGIC
12.1. Check that there is no logic input diagnostic message on the display.
12.2. Set the monitored contact for the logic input programmed in setpoint
message User Input A Source to the closed state and the virtual input to
the on state. Check that the diagnostic message, either User Input A or
the name programmed in setpoint User Input A Name, appears on the
display with the Auxiliary LED and relay activated. Check in the Event
Recorder that the selected function has been invoked.
12.3. Leave the monitored contact in the closed state and put the virtual input
in the off state. Check that the diagnostic message, the Auxiliary LED and
relay remain activated.
12.4. Set the monitored contact to the open state and leave the virtual input in
the off state. Check that the diagnostic message, the Auxiliary LED and
relay remain activated.
12.5. Leave the monitored contact in the open state and put the virtual input in
the on state. Check that the diagnostic message is removed from the dis-
play with the Auxiliary LED and relay deactivated.
12.6. Repeat steps 12.3 through 12.5 for all functions programmed to be
asserted by a Closed | Voff input.
13. For
INPUT ASSERTED LOGIC
13.1. Set the monitored contact for the logic input programmed in setpoint
message User Input A Source to the open state and the virtual input to
the off state. Check that the diagnostic message, either User Input A or
the name programmed in setpoint User Input A Name, appears on the
display with the Auxiliary LED and relay activated. Check in the Event
Recorder that the selected function has been invoked.
13.2. Leave the monitored contact in the open state and put the virtual input in
the on state. Check that the diagnostic message, the Auxiliary LED and
relay remain activated.
http://www.GEmultilin.com
setpoints set to "Closed | Von":
setpoints set to "Closed | Voff":
setpoints set to "Open | Von":