750/760
Feeder Management Relay
POST FAULT
VALUES

Factory Service

FACTORY
SERVICE
5–138
PHASE C CURRENT
MESSAGE
LEVEL: 1.00 x CT
PHASE C CURRENT
MESSAGE
POSITION: 300° Lag
GND CURRENT
MESSAGE
LEVEL: 0.00 x CT
GND CURRENT
MESSAGE
POSITION:
SENSTV GND CURRENT
MESSAGE
LEVEL: 0.100 x CT
SENSTV GND CURRENT
MESSAGE
POSITION:
SYSTEM FREQ:
MESSAGE
60.00 Hz
A/I
MESSAGE
CURRENT: 0.00 mA
The Fault Simulation State allows adjustment of all current and voltage phasors so
that a wide variety of system disturbances can be simulated. The frequency and the
analog input values can also be adjusted to give complete flexibility. Fault bus
voltage values are always entered as Wye values, even if the relay is set to Delta.
The relay will calculate the equivalent line voltages. Voltage magnitudes are entered
in per unit values relative to the nominal system voltage that is defined by the
NOMINAL VT SECONDARY VOLTAGE
are entered in per unit values relative to the nominal system current that is defined
by the
setpoint. All phasor angles are referenced to the prefault A-
PHASE CT PRIMARY
N bus voltage at 0°.
e) Postfault Values
PATH: SETPOINTS
S8 TESTING
[ ]
BUS VOLTAGE
LEVEL: 1.00 x VT
BUS VOLTAGE
MESSAGE
FREQ: 60.00 Hz
SYNC VOLTAGE
MESSAGE
LEVEL: 1.00 x VT
SYNC VOLTAGE
MESSAGE
POSITION:
SYNC VOLTAGE
MESSAGE
FREQ: 60.00 Hz
The Postfault State allows adjustment of the bus and line voltages in order to
simulate an open breaker condition and allow testing of the synchrocheck feature.
All phasor angles are referenced to the prefault A-N bus voltage at 0°.
PATH: SETPOINTS
S8 TESTING
[ ]
ENTER FACTORY
PASSCODE:
These messages are intended for factory use only, to perform testing and
diagnostics. Entering the factory service passcode in the first message allows access
to the command messages.
http://www.GEmultilin.com
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0 to 359° Lag in steps of 1
Range: 0.00 to 20.00 x CT in steps of
0.01
Range: 0 to 359° Lag in steps of 1
0° Lag
Range: 0.000 to 1.000 x CT in steps of
0.001
Range: 0 to 359° Lag in steps of 1
0° Lag
Range: 20.00 to 65.00 Hz in steps of
0.01
Range: 0.00 to 20.00 mA in steps of
0.01
and
setpoints. Phase current magnitudes
VT RATIO
SIMULATION
POSTFAULT VALUES
Range: 0.00 to 2.00 x VT in steps of
0.01
Range: 20.00 to 65.00 Hz in steps of
0.01
Range: 0.00 to 2.00 x VT in steps of
0.01
Range: 0 to 359° Lag in steps of 1
0° Lag
Range: 20.00 to 65.00 Hz in steps of
0.01
FACTORY SERVICE
Range: Restricted
personnel only
S8 Testing
access
for
GE
GE Multilin