S8 Testing

Output Relays

OUTPUT RELAYS
GE Multilin
S8 Testing
PATH: SETPOINTS
S8 TESTING
[ ]
FORCE OUTPUT RELAYS
FUNCTION: Disabled
FORCE 1 TRIP
MESSAGE
RELAY: De-energized
FORCE 2 CLOSE
MESSAGE
RELAY: De-energized
FORCE 3 AUX
MESSAGE
RELAY: De-energized
FORCE 4 AUX
MESSAGE
RELAY: De-energized
FORCE 5 AUX
MESSAGE
RELAY: De-energized
FORCE 6 AUX
MESSAGE
RELAY: De-energized
FORCE 7 AUX
MESSAGE
RELAY: De-energized
FORCE 8 SELF-TEST
MESSAGE
RELAY: De-energized
FORCE SOLID STATE
MESSAGE
OUTPUT: De-energized
For testing purposes, the relay provides the ability to override the normal function of
the solid state and output contacts. This is done by forcing each to energize or de-
energize.
Set
FORCE OUTPUT RELAYS FUNCTION
the solid state and output contacts, with the state programmed in the messages
that follow. Note that this setpoint will always be defaulted to the "Disabled" state at
power up.
Select "De-energized" for the remaining setpoints to force the output relays to the
de-energized state while
Selecting "Energized" forces the output relay to the energized state while the
setpoint is "Enabled".
OUTPUT RELAYS FUNCTION
http://www.GEmultilin.com
OUTPUT RELAYS
Range: Enabled, Disabled
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
Range: Energized, De-energized
to "Enabled" to override the normal operation of
FORCE OUTPUT RELAYS FUNCTION
750/760
Feeder Management Relay
is set to "Enabled".
FORCE
5–133