GE 750 Instruction Manual page 190

Feeder management relay
Hide thumbs Also See for 750:
Table of Contents

Advertisement

750/760
Feeder Management Relay
COIL MONITOR 1
5–94
e) Coil Monitor
PATH: SETPOINTS
S6 MONITORING
[ ]
COIL MON 1 NAME:
Trip Coil Monitor
COIL MON 1
MESSAGE
FUNCTION: Disabled
COIL MON 1
MESSAGE
RELAYS (3-7): -----
BREAKER STATE
MESSAGE
BYPASS: Disabled
COIL MON 1
MESSAGE
DELAY: 5 s
COIL MON 1
MESSAGE
TYPE: Trip
Coil Monitor 1 and 2 are programmed in this subgroup. They are two identical
elements that may be used to monitor trip or close coils. The operation of this
feature is described in Trip/Close Coil Supervision on page 3–12.
Detection of a failed circuit regardless of the breaker state (i.e. detection of a failed
trip circuit when the breaker is open) requires
Generally, this selection will require a wiring modification of the breaker, as detailed
in Trip/Close Coil Supervision on page 3–12.
FIGURE 5–54: Coil Monitor Logic
http://www.GEmultilin.com
EQUIPMENT
COIL MONITOR 1(2)
Range: Any
combination
alphanumeric characters.
Range: Disabled,
Alarm, Control
Range: Any combination of 3 to 7
Auxiliary relays
Range: Enabled, Disabled
Range: 5 to 100 s in steps of 1
Range: Trip, Close
BRKR STATE BYPASS
S6 Monitoring
of
18
Alarm,
Latched
to be "Enabled".