750/760
Feeder Management Relay

Outputs

Output Relays

CPU

2–12
TRANSFER SCHEME
Applicability: Used for double-bus system
with two normally-closed
incoming and one normally-
open bus tie circuit breaker.
Closing:
Automatic closing of the bus
tie breaker after a loss of one
source, with bus decayed
voltage permissive.
Trip:
Trips a pre-selected breaker
after the third breaker is
manually closed (prevent
parallel operation).
ANALOG OUTPUTS
Type:
Active
Outputs:
8 Channels; specify one of the
following output ranges when
ordering:
Ranges:
0 to 1 mA, 0 to 5 mA, 0 to 10
mA, 4 to 20 mA
Max. load:
12 kΩ for 0 to 1 mA output,
2.4 kΩ for 0 to 5 mA output,
1.2 kΩ for 0 to 10 mA output,
600 Ω for 4 to 20 mA output
Isolation:
Fully isolated
Accuracy:
±1% of full scale
Response:
100% indication in less than 6
power system cycles (100 ms
at 60 Hz)
Relay contacts must be considered unsafe to touch when the 750/
760 is energized! If the output relay contacts are required for low
voltage accessible applications, it is the customer's responsibility to
WARNING
ensure proper insulation levels.
CONFIGURATION
Number:
8
Type:
Form A: Trip (1) and Close (2)
Relays
Form C: Auxiliary Relays 3 to 7
and Self-Test Warning Relay 8
Contacts:
silver alloy
Durability:
100 000 operations (at 1800
operations/hour) at rated load
FORM A CONTACT RATINGS
Applicability: Trip and Close Relays (relays 1
and 2)
Make:
30 A (per ANSI/IEEE C37.90)
Carry:
20 A continuous
Break (DC):
300 W resistive,
150 W inductive (L/R = 40 ms)
Break (AC):
5000 VA resistive
5000 VA inductive (PF = 0.4)
COMMUNICATIONS
Baud rate:
300 to 19200 baud
Parity:
programmable
Protocol:
Modbus RTU or DNP 3.0
Ethernet:
10Base-T RJ45 connector
Modbus TCP/IP
Version 2.0 / IEEE 802.3
http://www.GEmultilin.com
Specifications
AUTORECLOSE (760 ONLY)
Reclose attempts: Up to four (4) before
lockout.
Blocking:
Each reclose shot can block
IOC and raise TOC Pickup.
Adjustability: Current supervision can adjust
the maximum number of shots
to be attempted.
SOLID STATE TRIP
Make & carry: 15 A at 250 V DC for 500 ms
FORM C CONTACT RATINGS
Applicability: Auxiliary Relays 3 to 7; Self-
Test Warning Relay (relay 8)
Make:
30 A (per ANSI/IEEE C37.90)
Carry:
10 A for 15 seconds
5 A continuous
Break (DC):
150 W resistive,
90 W inductive (L/R = 40 ms)
Break (AC):
1250 VA resistive
500 VA inductive (PF = 0.4)
EEPROM
100000 program/erase cycles max.
CLOCK
Resolution:
1 ms
Accuracy with IRIG-B:±1 ms
Accuracy without IRIG-B: ±1 minute/month
Supercap backup life: 45 days when control
power is off