S6 Monitoring

Fault Locator

FAULT LOCATOR
GE Multilin
FIGURE 5–39: Power Factor Logic
PATH: SETPOINTS
S6 MONITORING
[ ]
LENGTH OF FEEDER:
0.1 km
UNITS OF LENGTH:
MESSAGE
km
Zpos (RESISTIVE) OF
MESSAGE
FEEDER: 0.01
Zpos (INDUCTIVE) OF
MESSAGE
FEEDER: 0.01
Zzero (RESISTIVE) OF
MESSAGE
FEEDER: 0.01
Zzero (INDUCTIVE) OF
MESSAGE
FEEDER: 0.01
FAULT TYPE OUTPUT TO
MESSAGE
RELAYS 4-7: Disabled
FAULT LOCATION AFTER
MESSAGE
TRIP: Disabled
The relay calculates the distance to fault with fault resistance compensation. For the
fault location feature, a fault is defined as an event that has caused a current level
greater than the pickup threshold of an overcurrent protection feature programmed
to "Trip" or "Trip & AR" (760 only), which has remained for sufficient time to cause
the relay to produce a Trip command. After this has happened, the apparent
distance to the fault is calculated in a background mode, maintaining all other
features in operation. The distance calculation is based on the assumptions that:
http://www.GEmultilin.com
Feeder Management Relay
FAULT LOCATOR
Range: 0.1 to 99.9 km/Miles in steps of
0.1
Range: km, Miles
Range: 0.01 to 99.99 Ω in steps of 0.01
Ω
Range: 0.01 to 99.99 Ω in steps of 0.01
Ω
Range: 0.01 to 99.99 Ω in steps of 0.01
Ω
Range: 0.01 to 99.99 Ω in steps of 0.01
Ω
Range: Disabled, Enabled
Range: Disabled, Enabled
750/760
5–77