S4 Output Relays
Trip Relay
1 TRIP RELAY
GE Multilin
PATH: SETPOINTS
S4 OUTPUT RELAYS
[ ]
TRIP RELAY SEAL IN
TIME: 0.04 s
A
can be programmed for the Trip Relay. This time is added to
TRIP RELAY SEAL IN TIME
the reset time of the Trip Relay, thus extending its pulse width. This is for use in
applications where the 52 contacts reporting breaker state to the 750/760 are faster
than the 52 contacts that are responsible for interrupting coil current.
FIGURE 5–1: Output Relay 1 Trip Logic
http://www.GEmultilin.com
Feeder Management Relay
1 TRIP RELAY
Range: 0.00 to 9.99 s in steps of 0.01
750/760
5–29