Close Relay - GE 750 Instruction Manual

Feeder management relay
Hide thumbs Also See for 750:
Table of Contents

Advertisement

750/760
Feeder Management Relay

Close Relay

2 CLOSE RELAY
5–30
PATH: SETPOINTS
S4 OUTPUT RELAYS
[ ]
CLOSE RELAY SEAL IN
TIME: 0.04 s
A
CLOSE RELAY SEAL IN TIME
added to the reset time of the Close Relay, thus extending its pulse width. This is for
use in applications where the 52 contacts reporting breaker state to the 750/760
are faster than the 52 contacts that are responsible for interrupting coil current.
FIGURE 5–2: Output Relay 2 Close Logic
http://www.GEmultilin.com
2 CLOSE RELAY
Range: 0.00 to 9.99 s in steps of 0.01
can be programmed for the Close Relay. This time is
S4 Output Relays
GE Multilin

Advertisement