S5 Protection
NEG SEQUENCE
INST OVERCURRENT
GE Multilin
c) Negative Sequence Instantaneous Overcurrent
PATH: SETPOINTS
S5 PROTECTION
[ ]
NEG SEQ INST OC
FUNCTION: Disabled
NEG SEQ INST OC
MESSAGE
RELAYS (3-7): -----
NEG SEQ INST OC
MESSAGE
PICKUP: 1.000 x CT
NEG SEQ INST OC
MESSAGE
DELAY: 0.00 s
NEG SEQ INST OC
MESSAGE
DIRECTION: Disabled
A instantaneous overcurrent element operating on the negative sequence
component of current, ANSI device 46 is programmed in this subgroup.
FIGURE 5–24: Negative Sequence IOC Logic
http://www.GEmultilin.com
Feeder Management Relay
NEGATIVE SEQUENCE
NEG SEQUENCE INST...
Range: Disabled, Trip, Trip & AR,
Alarm, Latched Alarm, Control
Range: Any combination of 3 to 7
Auxiliary relays
Range: 0.05 to 20.00 x CT in steps of
0.001
Range: 0.00 to 600.00 s in steps of 0.01
Range: Disabled, Forward, Reverse
750/760
5–61