Specifications; Applicability; Inputs - GE Multilin 745 Instruction Manual

Transformer management relay
Table of Contents

Advertisement

745
Transformer Management Relay

Applicability

Inputs

2–4

Specifications

Transformers: 2 Winding or 3 Winding
Frequency:
50 or 60 Hz nominal
(frequency tracking allows
operation from 2 to 65 Hz)
CONTROL POWER
Options:
LO/HI (specified when
ordering)
LO range:
20 to 60 V DC;
20 to 48 V AC at 48 to 62 Hz
HI range:
90 to 300 V DC;
70 to 265 V AC at 48 to 62 Hz
Power:
30 VA nominal, 40 VA max.
Fuse (not accessible)
Current Rating: 3.15 A
Type:
5 × 20 mm Slow-Blow
Littelfuse, High Breaking
Capacity; Model # 2153.15
PHASE CURRENT INPUT
Source CT:
1 to 50000 A primary
1 or 5 A secondary
Relay input:
1 A or 5 A (specified at order)
Burden:
Less than 0.2 VA at rated load
per phase
Conversion range: 0.02 to 46 × CT
Accuracy:
at < 4 × CT: ±0.25% of 4 × CT (±0.01 ×CT)
at ≥ 4 × CT: ±0.5% of 46 × CT (±0.2 × CT)
Overload withstand: 1 second at 80 times
rated current; 2 seconds at 40
times rated current;
continuous at 3 times rated
current
GROUND CURRENT INPUT
Source CT:
1 to 50000 A primary
1 or 5 A secondary
Relay input:
1 A or 5 A (specified at order)
Burden:
less than 0.2 VA at rated load
Conversion range: 0.02 to 46 × CT
Accuracy:
at < 4 × CT: ±0.25% of 4 × CT (±0.01 ×CT)
at ≥ 4 × CT: ±0.5% of 46 × CT (±0.2 × CT)
Overload Withstand: 1 second at 80 times
rated current; 2 seconds at 40
times rated current;
continuous at 3 times rated
current
http://www.GEindustrial.com/multilin
Specifications
VOLTAGE INPUTS
Source VT:
2 to 600 kV / 60 to 120 V
Source VT ratio: 1 to 5000 in steps of 1
Relay Input: 60 V to 120 V phase-neutral
Burden:
Less than 0.025 VA at 120 V
Max. continuous: 273 V
Accuracy:
±1% of 2 × VT (±0.02 × VT)
LOGIC INPUTS
Number of inputs: 16
Dry contacts: 1000 Ω maximum ON
resistance (32 V DC at 2 mA
provided by the 745)
Wet contacts: 30 to 300 V DC at 1.5 mA
ANALOG INPUT
Type:
DC mA
Ranges:
0 to 1 mA, 0 to 5 mA, 0 to 10
mA, 0 to 20 mA, 4 to 20 mA
(programmable)
Input impedance: 375 Ω ±10%
Conversion range: 0 to 21 mA
Accuracy:
±1% of full scale (based on
input range)
TAP POSITION
Type:
resistance (ohms)
Range:
0 to 500 Ω or 0.5 to 5.0 kΩ
Bias current: 1 mA or 10 mA (based on
input range)
Accuracy:
±1% of full scale (based on
input range)
RTD
Type:
3 wire
RTD Type
100 Ω Platinum (DIN.43760),
100 Ω Nickel, 120 Ω Nickel
IRIG-B INPUT
Amplitude-modulated: 1.0 to 10 V pk-pk
DC shift:
TTL
Input impedance: 70 to 100 kΩ
GE Multilin

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents