750/760
Feeder Management Relay
7–54
close, Output Relay 4 should reset and Output Relays 5 and 7 on the Incomer 1
relay should operate.
11. Assert Logic Input 5 (Breaker Connected) at the Incomer 2 relay - nothing
should happen.
12. Assert Logic Input 2 (Remote Close) at the Incomer 2 relay - nothing should
happen. Energize Source 2 at nominal voltage - the Incomer 2 breaker should
close, Output Relay 4 should reset and Output Relays 5 and 7 on the Incomer 2
relay should operate.
13. De-assert Logic Input 5 (Breaker Connected) at the Bus Tie relay - Output
Relays 4 and 6 on the Bus Tie relay should reset, and at both Incomer relays the
message Transfer Not Ready should be displayed.
14. Assert Logic Input 5 (Breaker Connected) at the Bus Tie relay - Output Relays 4
and 6 on the Bus Tie relay should operate, and at both Incomer relays the
message Transfer Not Ready should be removed from the display.
15. De-assert Logic Input 5 (Breaker Connected) at the Incomer 1 relay; at the
Incomer 1 relay Output Relays 5 and 7 should reset; at both Incomer relays the
message Transfer Not Ready should be displayed.
16. Assert Logic Input 5 (Breaker Connected) at the Incomer 1 relay; at the
Incomer 1 relay Output Relays 5 and 7 should operate; at both Incomer relays
the message Transfer Not Ready should be removed from the display.
17. Momentarily assert Logic Input 3 (Remote Open) at the Incomer 1 relay; the
Incomer 1 breaker should trip and Output Relays 5 and 7 should reset; at both
Incomer relays the message Transfer Not Ready should be displayed.
18. Momentarily assert Logic Input 2 (Remote Close) at the Incomer 1 relay; the
Incomer 1 breaker should close and Output Relays 5 and 7 should operate; at
both Incomer relays the message Transfer Not Ready should be removed.
19. De-assert Logic Input 5 (Breaker Connected) at the Incomer 2 relay; at the
Incomer 2 relay Output Relays 5 and 7 should reset; at both Incomer relays the
message Transfer Not Ready should be displayed.
20. Assert Logic Input 5 (Breaker Connected) at the Incomer 2 relay; at the
Incomer 2 relay Output Relays 5 and 7 should operate; at both Incomer relays
the message Transfer Not Ready should be removed from the display.
21. Momentarily assert Logic Input 3 (Remote Open) at the Incomer 2 relay; the
Incomer 2 breaker should trip and Output Relays 5 and 7 should reset; at both
Incomer relays the message Transfer Not Ready should be displayed.
22. Momentarily assert Logic Input 2 (Remote Close) at the Incomer 2 relay; the
Incomer 2 breaker should close and Output Relays 5 and 7 should operate; at
both Incomer relays, the Transfer Not Ready message should disappear.
23. Momentarily assert Logic Input 2 (Remote Close) at the Bus Tie relay; the Bus
Tie breaker should close and Output Relays 5 and 7 should operate; at both
Incomer relays the Transfer Not Ready message should be displayed.
24. Momentarily assert Logic Input 3 (Remote Open) at the Bus Tie relay; the Bus
Tie breaker should trip and Output Relays 5 and 7 should reset, and at both
Incomer relays the Transfer Not Ready message should disappear.
25. Assert Logic Input 11 (Block Transfer) at the Incomer 1 relay; Output Relays 5
and 7 should reset; at both Incomer relays the Transfer Not Ready message
should be displayed.
26. De-assert Logic Input 11 (Block Transfer) at the Incomer 1 relay; Output Relays
5 and 7 should operate; at both Incomer relays the Transfer Not Ready message
should be removed from the display.
27. Assert Logic Input 11 (Block Transfer) at the Incomer 2 relay; Output Relays 5
and 7 should reset; at both Incomer relays the Transfer Not Ready message
should be displayed.