Panasonic minas a4 series Instruction Manual page 123

Ac servo motor and driver
Hide thumbs Also See for minas a4 series:
Table of Contents

Advertisement

PrNo.
Title
61
Zero-speed
63
Setup of
positioning
complete
(In-position)
output
65
LV trip selection at
main power OFF
66
Sequence at
*
over-travel inhibit
<Notes>
• For parameters which No. have a suffix of "*", changed contents will be validated when you turn on the
control power.
[Connection and Setup of Position Control Mode]
Setup
Unit
range
You can set up the timing to feed out the zero-speed detection output signal
10 to
r/min
(ZSP : CN X5, Pin-12 or TCL : CN X5, Pin-40) in rotational speed [r/min].
20000
The zero-speed detection signal (ZSP) will be fed out when the motor
<50>
speed falls below the setup of this parameter, Pr61.
• The setup of P61 is valid for both
CCW and CW direction regardless
of the motor rotating direction.
• There is hysteresis of 10 [r/min].
0 to 3
You can set up the action of the positioning complete signal (COIN : Pin-
39 of CN X5) in combination with Pr60 (Positioning complete range).
<0>
Setup value
<0>
1
2
3
0 to 1
You can select whether or not to activate Err13 (Main power under-
voltage protection) function while the main power shutoff continues for the
<1>
setup of Pr6D (Main power-OFF detection time).
Setup value
0
<1>
<Caution>
This parameter is invalid when Pr6D (Detection time of main power
OFF)=1000. Err13 (Main power under-voltage protection) is triggered
when setup of P66D is long and P-N voltage of the main converter falls
below the specified value before detecting the main power shutoff,
regardless of the Pr65 setup. Refer to P.42, "Timing Chart-At Power-ON"
of Preparation as well.
You can set up the running condition during deceleration or after stalling,
0 to 2
while over-travel inhibit input (CCWL : Connector CN X5, Pin-9 or CWL :
<0>
Connector CN X5, Pin-8) is valid
Setup value
<0>
1
2
<Caution>
In case of the setup value of 2, torque limit during deceleration will be
limited by the setup value of Pr6E (Torque setup at emergency stop ).
Function/Content
ZSP
Action of positioning complete signal
The signal will turn on when the positional deviation is smaller
than Pr60 (Positioning complete range)
The signal will turn on when there is no position command and the
positional deviation is smaller than Pr60 (Positioning complete range).
The signal will turn on when there is no position command, the
zero-speed detection signal is ON and the positional deviation is
smaller than Pr60 (Positioning complete range).
The signal will turn on when there is no position command and the
positional deviation is smaller than Pr60 (Positioning complete range).
Then holds "ON" status until the next position command is entered.
Action of main power low voltage protection
When the main power is shut off during Servo-ON, Err13 will
not be triggered and the driver turns to Servo-OFF. The driver
returns to Servo-ON again after the main power resumption.
When the main power is shut off during Servo-ON, the driver
will trip due to Err13 (Main power low voltage protection).
During deceleration
After stalling
Dynamic brake
Torque command=0
action
towards inhibited direction
Torque command=0
Torque command=0
towards inhibited direction
towards inhibited direction
Torque command=0
Emergency stop
towards inhibited direction
Standard default : < >
CCW
speed
(Pr61+10)r/min
(Pr61–10)r/min
CW
ON
Deviation counter content
Hold
Hold
Clears before/
after deceleration
121