5 SETTINGS
c) REMOTE DEVICES: ID OF DEVICE FOR RECEIVING GSSE MESSAGES
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE DEVICE
1
MESSAGE
MESSAGE
Sixteen remote devices, numbered from 1 to 16, can be selected for setting purposes. A receiving relay must be pro-
grammed to capture messages from only those originating remote devices of interest. This setting is used to select specific
remote devices by entering (bottom row) the exact identification (ID) assigned to those devices.
The
REMOTE DEVICE 1(16) ETYPE APPID
sages. This setting identifies the Ethernet application identification in the GOOSE message. It should match the corre-
sponding settings on the sending device.
The
REMOTE DEVICE 1(16) DATASET
DNA and UserSt bit pairs), or one of the configurable datasets.
Note that the dataset for the received data items must be made up of existing items in an existing logical node. For this rea-
son, logical node GGIO3 is instantiated to hold the incoming data items. GGIO3 is not necessary to make use of the
received data. The remote input data item mapping takes care of the mapping of the inputs to remote input FlexLogic™
operands. However, GGIO3 data can be read by IEC 61850 clients.
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE INPUT 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
Remote Inputs which create FlexLogic™ operands at the receiving relay, are extracted from GSSE/GOOSE messages
originating in remote devices. Each remote input can be selected from a list consisting of 64 selections: DNA-1 through
DNA-32 and UserSt-1 through UserSt-32. The function of DNA inputs is defined in the IEC 61850 specification and is pre-
sented in the IEC 61850 DNA Assignments table in the Remote Outputs section. The function of UserSt inputs is defined by
the user selection of the FlexLogic™ operand whose state is represented in the GSSE/GOOSE message. A user must pro-
gram a DNA point from the appropriate FlexLogic™ operand.
Remote Input 1 must be programmed to replicate the logic state of a specific signal from a specific remote device for local
use. This programming is performed via the three settings shown above.
The
setting allows the user to assign descriptive text to the remote input. The
REMOTE INPUT 1 ID
selects the number (1 to 16) of the remote device which originates the required signal, as previously assigned to the remote
device via the setting
REMOTE DEVICE 1(16) ID
specific bits of the GSSE/GOOSE message required.
The
REMOTE IN 1 DEFAULT STATE
the remote device sending the point is declared to be non-communicating. The following choices are available:
GE Multilin
REMOTE DEVICES
REMOTE DEVICE 1(16)
REMOTE DEVICE
1 ID:
Remote Device 1
REMOTE DEVICE
1
ETYPE APPID: 0
REMOTE DEVICE
1
DATASET: Fixed
setting is only used with GOOSE messages; they are not applicable to GSSE mes-
setting provides for the choice of the G60 fixed (DNA/UserSt) dataset (that is, containing

REMOTE INPUTS

REMOTE INPUT 1(32)
REMOTE INPUT
1 ID:
Remote Ip
1
REMOTE IN
1 DEVICE:
Remote Device
1
REMOTE IN
1 ITEM:
None
REMOTE IN
1 DEFAULT
STATE: Off
REMOTE IN
1
EVENTS: Disabled
(see the Remote Devices section). The
setting selects the logic state for this point if the local relay has just completed startup or
G60 Generator Management Relay
5.7 INPUTS/OUTPUTS
Range: up to 20 alphanumeric characters
Range: 0 to 16383 in steps of 1
Range: Fixed, GOOSE 1 through GOOSE 8
5.7.6 REMOTE INPUTS
Range: up to 12 alphanumeric characters
Range: 1 to 16 inclusive
Range: None, DNA-1 to DNA-32, UserSt-1 to UserSt-32,
Config Item 1 to Config Item 64
Range: On, Off, Latest/On, Latest/Off
Range: Disabled, Enabled
REMOTE IN 1 DEVICE
REMOTE IN 1 ITEM
5
setting
setting selects the