Egd Protocol Status; Teleprotection Channel Tests - GE G60 Instruction Manual

Ur series generator management relay
Hide thumbs Also See for G60:
Table of Contents

Advertisement

6.2 STATUS
a) FAST EXCHANGE
PATH: ACTUAL VALUES
FAST EXCHANGE 1
6
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the fast EGD exchange is displayed.
b) SLOW EXCHANGE
PATH: ACTUAL VALUES
SLOW EXCHANGE 1
These values provide information that may be useful for debugging an EGD network. The EGD signature and packet size
for the slow EGD exchanges are displayed.
PATH: ACTUAL VALUES
TELEPROT CH TESTS
The status information for two channels is shown here.
CHANNEL 1(2) STATUS: This represents the receiver status of each channel. If the value is "OK", teleprotection is
enabled and data is being received from the remote terminal; If the value is "FAIL", teleprotection enabled and data is
not being received from the remote terminal. If "n/a", teleprotection is disabled.
CHANNEL 1(2) LOST PACKETS: Data is transmitted to the remote terminals in data packets at a rate of 2 packets per
cycle. The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS
CLEAR RECORDS
VALIDITY OF CHANNEL CONFIGURATION: This value displays the current state of the communications channel
identification check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the
"FAIL" message will be displayed. The "N/A" value appears if the local relay ID is set to a default value of "0", the chan-
nel is failed, or if the teleprotection inputs/outputs are not enabled.
6-8
STATUS

EGD PROTOCOL STATUS

FAST EXCHANGE 1
SIGNATURE:
FAST EXCHANGE 1
MESSAGE
DATA LENGTH:
STATUS
EGD PROTOCOL STATUS
SLOW EXCHANGE 1
SIGNATURE:
SLOW EXCHANGE 1
MESSAGE
DATA LENGTH:
STATUS
TELEPROT CH TESTS
CHANNEL 1
STATUS: n/a
CHANNEL 1 LOST
MESSAGE
PACKETS:
CHANNEL 2
MESSAGE
STATUS: n/a
CHANNEL 2 LOST
MESSAGE
PACKETS:
VALIDITY OF CHANNEL
MESSAGE
CONFIGURATION: FAIL
menu.
G60 Generator Management Relay
PRODUCER STATUS
FAST EXCHANGE 1
0
0
PRODUCER STATUS
SLOW EXCHANGE 1(2)
0
0

6.2.15 TELEPROTECTION CHANNEL TESTS

Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
Range: 1 to 65535 in steps of 1
1
Range: n/a, FAIL, OK
6 ACTUAL VALUES
6.2.14 EGD PROTOCOL STATUS